AAAC Bare Conductor BS EN50182

AAAC Bare Conductor BS EN50182
Product Detailed
Related Categories:Power Cables
AAAC Bare Conductor BS EN50182 ISO9001 & ISO14001 Prompt delivery, direct factory price FREE SAMPLES

AAAC Bare Conductor BS EN50182

1. The features of aluminum alloy power cable

1.1. Power consumption in transit depends on the conductor resistance instead of the resistivity.

1.2. Under the same current capacity, the cross section of aluminum alloy cable is 1.6 times than that of the copper conductor cable.

1.3. Under the same current capacity, the diameter of aluminum alloy conductor is about 1.2 times of copper conductor.

1.4. Under the same equivalent cross section length, the weight of aluminum conductor is 50% of copper conductor.

1.5. Good performance of joint (Owing to the adding of several elements such as iron, magnesium, rare earth to aluminum. 

1.6. Improvement of the mechanical performance 

1.7. High strength: The alloying increases the tensile strength of aluminum alloy.

1.8. Strong elongation: The elongation is above 25%, which greatly improves the bending performance.  

1.9. Small resiliency: The resiliency of aluminum alloy cable is 40% less than that of copper cable, so it is convenient and safe for construction.

1.10. Creep-resisting: The special alloy of aluminum alloy conductor and heat treatment process largely reduce the tendency of mental creep when it is under heat and pressure.  

The sheet showed below is AAAC Bare Conductor Technical Characters Based on Standard BS EN50182  

  
Code Old CodeCross sectionNo. of wiresDiameterMass per unit lengthRated strengthDC resistance at 20°C
WireConductor
mm2 mmmmkg/kmKNohm/km
19-Al3BOX18.871.855.5551.45.551.7480
24-Al3ACACIA23.872.086.2464.97.021.3828
30-Al3ALMOND30.172.347.0282.28.881.0926
35-Al3CEDAR35.572.547.6296.810.460.9273
42-Al3DEODAR42.272.778.31115.212.440.7797
48-Al3FIR47.872.958.85130.614.110.6875
60-Al3HAZEL59.973.309.90163.417.660.5494
72-Al3PINE71.673.6110.80195.621.140.4591
84-Al3HOLLY84.173.9111.70229.524.790.3913
90-Al3WILLOW89.774.0412.10245.026.470.3665
119-Al3OAK118.974.6514.00324.535.070.2767
151-Al3MULBERRY150.9193.1815.90414.344.520.2192
181-Al3ASH180.7193.4817.40496.153.310.1830
211-Al3ELM211.0193.7618.80579.262.240.1568
239-Al3POPLAR239.4372.8720.10659.470.610.1387
303-Al3SYCAMORE303.2373.2322.60835.289.400.1095
362-Al3UPAS362.1373.5324.70997.5106.820.0917
479-Al3YEW479.0374.0628.401319.6141.310.0693
498-Al3TOTARA498.1374.1429.001372.1146.930.0666
587-Al3RUBUS586.9613.5031.501622.0173.130.0567
659-Al3SORBUS659.4613.7133.401822.5194.530.0505
821-Al3ARAUCARIA821.1614.1437.302269.4242.240.0406
996-Al3REDWOOD996.2614.5641.002753.2293.880.0334

AAAC Bare Conductor

 1). Standard: BS 3242, EN50182, ASTM B399, DIN48201,IEC, AS/NZS .

2). Application: AAAC are used in overhead electric power transmission and distribution lines.

3). We can meet customer's special needs.

  

            

AAAC Bare Conductor BS EN50182